📖 Description:
A digital overload and asymmetry relay designed for motor protection. It features manual, semi-automatic, and automatic reset options, ensuring flexibility in various applications. With a current range of 0.1–25A and 220VAC operating voltage, it provides reliable thermal protection against overload and phase asymmetry. Ideal for industrial automation and motor safety.
⚙️ Usage of Device and Working Principle:
Make the connection of the device according to the connection diagram. Energize the device after making the connections. The display shows the set values for 5 seconds when the device is energized.
-
Adjust the overload with the “A>” knob (value shown on the left display).
-
Set the delay time with the “t” knob (value shown on the left display).
-
When energized, the relay activates, contact output goes to terminal 3 and “OUT” LED turns on.
-
If current exceeds the set high current (A>), the device begins delay timing and shows ERR. After the delay, the relay deactivates, contact output switches to terminal 1, and “OUT” LED turns off.
⏱️ Delay Time (Start Current):
After the relay is energized or reset, the device does not control current for 5 seconds. This prevents false triggering during motor startup.
🔀 Asymmetry Detection:
If there’s over 50% difference between the highest and lowest phase currents, the device triggers an asymmetry fault within 2 seconds.
-
The affected phases’ display flashes.
-
Error LED lights up.
-
Below threshold values, asymmetry is not monitored.
🔁 Reset Modes:
Note: Press the SELECT button for 10 seconds to change the reset mode. The mode indicator will change.
⚠️ Warnings
-
Use the device according to the manual.
-
Do not operate in wet environments.
-
Include a switch and circuit breaker nearby for safety.
-
Label the switch and breaker clearly for device isolation.
-
Maximum current ratings:
-
TRM-03: 3A
-
TRM-12: 12A
-
TRN: 25A
Exceeding these may lead to inaccurate readings or device damage.
-
🧼 Maintenance
-
Turn off and disconnect the device before maintenance.
-
Clean connection points with a swab only.
-
Avoid conductive or corrosive chemicals.
-
Confirm correct operation after cleaning.
🔧 Technical Specifications
-
Operating Voltage: 110VAC / 150V–260VAC / 380VAC
-
Frequency: 50/60Hz
-
Power Consumption: <6VA
-
Temperature Range: -20℃ to +55℃
-
Display: 3×3 Digit Display, 5 LEDs
-
Asymmetry Threshold: 50% (Fixed)
-
Overload Range:
-
TRM-03: 0.1–3A
-
-
Delay Time (t):
-
0.1–10 sec (TRM-03~25)
-
1–200 sec (TRM-200~400)
-
-
Connection: Terminal
-
Contact Rating: 5A @ 250VAC (resistive load)
-
Cable Diameter: up to 2.5mm²
-
Weight: Max. 1210g
-
Mounting: DIN rail
-
Operating Altitude: <2000m