📖 Description:
An easy-to-use electronic overload relay designed for reliable motor protection. It safeguards motors against thermal overload, phase failure, and current imbalances, ensuring efficient performance and longevity. With an operating voltage range of 90-260VAC, it offers wide compatibility and adjustable protection settings. Its compact design and simple installation make it ideal for various industrial and automation applications.
⚙️ Features:
- ■ Compact Design
■ Overload / Phase Loss / Locked Rotor
Protection
■ Independently Adjustable Starting Trip Delay &
Operating Time
■ Wide Current Range:3-35A
■ Wide Operating Voltage Range
■ PWR & Trip Indication LED
■ Manual / Electric Reset
■ Ambient Insensitive
■ Low Energy Consumption
■(No Volt Release/Fail-safe Operation)→N Type
🛠️ Applications:
- – Low Voltage Induced Electromotor (600V Level)
Protective Relay
– Break-Down Watch Current Relay
– Alternative Replacement for the Existing Relay
Protection
- Protective Item Operating (Trip) TimeOver-Current = O-TIMEPhase Loss = O-TIMELocked Rotor = D-TIME+O-TIME
LED
- Ammeter Function:
After the motor runs smoothly, turn the overcurrent setting knob slowly counter clockwise to the red indicator light, which is 100% of the actual running current. And then turn the knob clockwise to just turn off the red light at this point for the actual running current value of about 103%.Run / Operation Indicator:
Relay Trip: Red LED
Power / normal operating status: Green LED
Manual / Electric Reset
- With test button ehld down,the red LED is on and the product will trip after O-TIME.The relay will be de-energized when RESET button is pushed or the control power is disconnected.
Set
- After the installation is complete the settings as follows.Set knob: D-TIME(Delay Time) Set two to three seconds longer than the motor starting time.Set knob: O-TIME(Over-current run time) Set less than the motor’s endurance time with over-current.Set knob: Load(Rated Current) Set over 110% of the motor’s rated current of under 120% of its operating current.
TEST Instruction
- With test button held down,the red LED is on and the product will trip after O-TIME.The relay will be de-energized when RESET button is pushed or the control power is disconnected.
LED Indication
- Item PWR(Green)LED Trip(Red)LEDPower ○ ×Normal Running ○ ×Trip × ○
Specifications
- Current Range .3-35AOperating Frequency….: 50/60HzOperating Power………..: <2WOperating Temperature: -20℃·····+55℃Waiting(t)………………….: D-Time 0.2-30s
O-Time 0.2-10sAsymmetry Set………….: %±10
Contact…………………….: 5A 250VAC Resistive Load
Connection Diagrams..: 35mm Din Rail(D) or Pane(P)